EXIT LED 1 is an IP65 emergency bulkhead for ceiling or wall: 150 lm through a reeded diffuser, or fit the ISO legend kit supplied and it becomes an exit sign with a 20m viewing distance. 20mm cable entries at both ends, centrally and at the rear; manual test / self-test or DALI-2. One fitting, two jobs.
Part-code builder
Pick one option in each position. Every combination shown is a valid build.
Features
- 01IP65 emergency bulkhead for ceiling or wall mounting
- 02150 lm in emergency through a reeded diffuser, 5500 K
- 03ISO legend kit supplied: an exit sign with a 20m viewing distance
- 04Maintained or non-maintained, 3 hours
- 05Combined manual test / self-test (BS EN 62034) or DALI-2 (DiiA registered)
- 063.2 V 1800 mAh LiFePO4 battery
- 07White polycarbonate housing, hinged gear tray; 20mm cable entries at both ends, centre and rear
- 08Class II; 350 x 110 x 60mm; 550 g
Specification
- IP
- IP65
- Controls
- ST (manual test / self-test), DALI (DALI-2)
- Emergency
- Integral, 3 hours
- Mounting
- Ceiling or wall
- Supply
- 230 V 50 Hz
- Electrical class
- Class II
- Dimensions
- 350 x 110 x 60mm; 550 g
- Warranty
- 5 years
Control gear, standards & warranty
- UKCA
- CE
- RoHS
- WEEE
- 230 V 50 Hz
- Class II
- IP65
- Emergency BS 5266-1
Integral emergency gear, 3 hours, LiFePO4 battery: combined manual test / self-test to BS EN 62034, or DALI-2 (DiiA registered) with automatic self-test. Designed to EN 60598-2-22. Arrow up (ISOAU, standard) is the British Standard sign for progress forward (BS 5499-4); on stairs the arrow follows the direction of travel. European arrow legend formats available on request.